What
should I look for in a supplier?
What
is IEEE-519?
It is the North American Standard that
describes acceptable limits of harmonics in electrical systems.
The proper reference is IEEE Std 519-1992, entitled "IEEE Recommended
Practices and Requirements for Harmonic Control in Electrical Power
Systems".
What will happen to my loads and electrical
system if I operate outside the IEEE 519 guidelines?
Perhaps nothing or maybe disaster! Systems
that operate above the guidelines are operating in a less reliable
environment. More problems occur than not. Some issues may be
immediate while others occur over the long term.
What is the Maximum Possible Neutral Current?
In a system feeding single-phase (phase-neutral)
loads using switching power supplies, such as 120V personal computers
and other electronic equipment, the worst case scenario for neutral
current is when the pulses drawn by the loads on each phase do
not overlap. The total resulting current in the neutral conductor
is the arithmetic sum, which is the root of the sum of the squares:
The maximum is reached when the loads are
balanced, so on a per unit basis, the result is: times the phase
current.
Any overlap of pulses between the phases,
and typically there is some, reduces the amount of neutral current
compared with the phase current.
Why do some people say neutral current can
reach 3 times phase current?
Over the past ten years, there have been many articles published
that mention neutral current, some mention 1.73 times at the maximum
possible level, some say 3 times, others say it can be 1.73 or
3 without any back-up. We have described how neutral current can
reach 1.73 times the phase current. The 3 times number comes from
simply summing the current from the 3 phases into the neutral
conductor (1+1+1 = 3). This reflects either a lack of understanding
of the requirement to do the root of the sum of the squares, or
contemplates that all loads draw only zero sequence 180Hz, not
consuming any fundamental (or other) current, obviously not possible
in our electrical systems.
What is a typical level
of Neutral Current for an Office Environment?
Today's offices are filled with desktop computers and laser printers.
Where these are the only loads fed from the local electrical panel,
neutral current can be expected to be in the range of 1.3 to 1.5
times the phase current. In many offices, the workspace cubicles
have a fluorescent task light that is plugged into the same system.
Since the harmonic content of an average fluorescent lamp is lower
than for a computer, it lowers the ratio of harmonics amps to
RMS amps, and this dilution reduced the expected neutral current
to about equal to the phase current. However, it should be noted
that if the task lighting uses compact fluorescent lamps, which
have a rich harmonic spectrum like a desktop computer, neutral
current can be expected to be in the 1.3-1.5 times the phase current.
Phase-shifting
is great but what if I have a single nonlinear load, like one
large motor drive?
The phase-shift technique relies on using the harmonic currents
produced by one load to cancel with the harmonic currents produced
by a similar but phase-shifted load. Phase-shifting will therefore
not work with a single harmonic producing load. Options for harmonic
treatment include active filters, tuned filters, reactors, or
moving the load to a dedicated feeder. Other treatments are possible.
The choice will depend on the results of an analysis of many variables
such as the electrical system characteristics, the load profile
and duty cycle.
What
are harmonics?
Harmonics are multiples of some base frequency, each having a
frequency and amplitude. For example our electrical system is
60 hertz so the 3rd harmonic is 180 hertz and the 5th harmonic
is 300 hertz. Each harmonic is sinusoidal and as such repeats
through a system.
What
causes harmonics?
Harmonic in our electrical systems today are caused by nonlinear
loads such as personal computers and variable speed drives. These
harmonics are introduced to the system through the way the load
draws current.
What
harmonics are most prevalent in today's electrical systems?
The loads that we place on our systems today are computers, laser
printers, video monitors, electronic ballasts, variable speed
drives and ups. Loads that are connected phase to neutral ( equipment
typically plugged into a wall receptacle) produce an abundance
of 3rd, 5th and 7th harmonic currents. Phase to phase and three
phase loads ( variable speed drives for example ) that are 6 pulse
produce mostly 5th and 7th harmonics.
What
are the effects of harmonics in an electrical system?
The most common issue is extra heat due to the additional losses.
Excessive neutral current will result in systems that have high
density of single phase loads due to the triplens (3rd harmonic
and its odd multiples) and the imbalance of the 60 hertz and the
other non triplen harmonic currents such as 5th and 7th. In systems
where the impedance is high voltage distortion will also become
an issue.
Why
do neutral conductors need to be oversized?
Single phase nonlinear loads carry a high amount of 3rd harmonic.
The 3rd harmonic is in phase in all three phases so they add into
the neutral. This can result in neutral current with a higher
value than the phase current. The large conductor is designed
to carry the additional expected current.
How
do I test for harmonics?
The most thorough way to test for harmonics is to take measurements
using a harmonic analyzer. Simple tests would include measuring
neutral to ground voltage at the panels and at the wall receptacles.
Take a simple meter and measure the neutral current. Also you
can compare the RMS readings to the non RMS readings.
After
collecting data how do I relate the measurements to an acceptable
standard?
IEEE 519 is the North American recommended practice for harmonic
levels. This practice recommend voltage distortion to be less
than 5% thd and no individual voltage to greater than 3%. It also
provides levels for current but only at the point of common coupling
( the point where the utility stops and in-house distribution
begins).
What
strategies are available for harmonic reduction?
Derating
Capacitors ( LC filters )
Phase shift ( change the pulse of the system )
Lower the impedance for zero sequence to shunt
Active
Reactors
Will
a K factor transformer reduce harmonics?
A K factor transformer is derated to survive
in a harmonic rich environment. It will not cancel any harmonic.
What are harmonic cancellation transformers?
These transformers if designed properly will
incorporate low zero sequence impedance and phase shifting, noise
reduction and higher efficiencies. They are used in place of isolation
and K rated transformers to cancel 3rd, 5th and 7th harmonic distortion.
What
should I look for in a supplier?
Application
support.
Quality of manufacture
Technical quality of product
Application experience
Installed base
Agency approvals